Armstrong Series 880 Inverted Bucket Steam Trap with Integral Strainer
Model 880 Model 881 Model 882 Model 883
Armstrong International (USA) Built-in Strainer Space & Cost Saving

Armstrong Series 880 Inverted Bucket Steam Trap with Integral Strainer

Two jobs, one compact body. The Series 880 pairs Armstrong’s proven inverted bucket mechanism with a stainless steel screen built directly into the trap. Pipe scale and rust are captured before they ever reach the valve — so you no longer need to buy, fit and maintain a separate Y-strainer upstream of every trap.

Max Operating Pressure
Up to 250 psig (17 bar)
Model 880 rated to 150 psig (10 bar)
Discharge Capacity
Up to 4,400 lb/hr (2,000 kg/hr)
Depends on model & orifice size
Design Rating
250 psig @ 450°F
17 bar @ 232°C
Connection Sizes
1/2″ to 1-1/4″
Screwed NPT / BSPT, horizontal
Why Choose the 880

Fewer Fittings, Fewer Leak Points, Less Downtime

Ideal for older steam networks where scale and debris are a daily reality.

Integrated Strainer Screen

A 304 stainless steel screen sits inside the inlet passage, catching scale and weld slag before they can wear the valve seat.

Compact Installation

Removing the separate strainer shortens the trap station, cuts two threaded joints and reduces labour on every drain point.

Easy Blow-Down & Cleaning

The screen is accessed through a dedicated cleanout plug, so maintenance teams can flush debris without dismantling the trap.

Inverted Bucket Toughness

Retains every strength of the bucket design: resistance to water hammer, automatic air & CO₂ venting and a water seal that prevents live steam loss.

Where It Fits Best

Typical Applications in Bangladeshi Plants

Many factories in Bangladesh run steam lines that are 10–20 years old. Rust flakes and scale travelling through those pipes are the number-one reason traps jam open and waste fuel. The 880 tackles this problem at the source.

  • Textile dyeing & finishing: winch & jet dyeing machines, drying cylinders, calendar rolls.
  • Garment washing plants: steam irons, tumble dryers, pressing tables and laundry presses.
  • Process heating: tank coils, jacketed vessels and small heat exchangers.
  • Steam main drips: drain pockets on headers and branch lines with heavy debris.

Available Options

Internal Check Valve (CV): stainless steel check valve prevents condensate backflow when the trap discharges into a lifted or pressurised return line.

Thermic Vent Bucket (T): speeds up air removal during cold start-ups, so equipment reaches temperature faster.

Scrub Wire: keeps the bucket vent hole clear in systems with heavy dirt load.

Series 880 Model Selection Guide

ModelPipe Sizes (NPT / BSPT)Max Operating PressureLoad Category
Model 8801/2″ (15 mm), 3/4″ (20 mm)150 psig (10 bar)Light loads
Model 8811/2″ (15 mm), 3/4″ (20 mm)250 psig (17 bar)Light to medium loads
Model 8823/4″ (20 mm), 1″ (25 mm)250 psig (17 bar)Medium loads
Model 8831″ (25 mm), 1-1/4″ (32 mm)250 psig (17 bar)Heavy loads – up to 4,400 lb/hr

Exact discharge capacity depends on the internal orifice chosen for your pressure differential. Our team will size the correct orifice for your application.

Materials of Construction

Body & CapCast Iron, ASTM A48 Class 30
InternalsAll stainless steel (304)
Valve & SeatHardened chrome steel
Strainer ScreenStainless steel (304) with cleanout plug
Max Back PressureUp to 99% of inlet pressure
InstallationHorizontal, side inlet / side outlet

Not Sure Between Series 800 and 880?

If your steam lines carry visible scale or you are short on installation space, the 880 is usually the smarter choice. Talk to our factory trained workforce for a free selection recommendation and quotation.