Low Profile Pump Trap – PT-3500 Series
Cast iron low-profile pump traps for condensate loads up to 14,400 lb/hr.
The PT-3500 Series is a non-electric pump trap for returning condensate from heat exchangers, coils, and remote equipment. Cast iron bodies carry allowable ratings of 150 psig and 450°F. Two models cover capacities from 9,900 to 14,400 lb/hr with 2-inch or 3-inch inlets.
Technical Specifications
Key technical data for the Low Profile Pump Trap – PT-3500 Series. Contact ALPHA INDUSTRIAL SERVICES for complete datasheets and sizing.
Additional Specifications
- Max operating pressure: 125 psig (8.5 barg)
- Body: ASTM A48 Class 30 cast iron
- Mechanism: stainless steel with Inconel X-750 spring
- Capacity: PT-3508 9,900 lb/hr (4,491 kg/hr); PT-3512 14,400 lb/hr (6,532 kg/hr)
- Inlet: 2 in (50 mm) on PT-3508; 3 in (75 mm) on PT-3512; outlet: 2 in (50 mm)
Typical Applications in Bangladesh
Recovers hot condensate to reduce fuel and water treatment costs.
Pumps condensate from below-steam-pressure equipment.
Flash tanks capture and reuse low-pressure flash steam.
Returns large condensate volumes from finishing machines.
Related Condensate Recovery

Low Boy™ Pump Trap Packages
Factory-packaged condensate return stations that combine an Armstrong pump trap with a low-profile receiver for dependable non-electric pumping.
View Details
Cast Iron Condensate Pump – 4700 Series
Floor-mounted cast iron condensate return units sized for light commercial and institutional steam heating loads.
View Details
Steel Condensate Pump – 4600 Series
Steel-receiver condensate return units built for loads from 2,000 to 50,000 square feet of radiation.
View Details
Steel Condensate Pump – 4800 Series
Stainless steel receiver condensate units for return service where corrosion resistance matters.
View DetailsNeed Technical Sizing or Steam Audit Support in Bangladesh?
Correct selection and sizing are critical to condensate drainage, pressure control, and energy savings. Contact the engineering team at ALPHA INDUSTRIAL SERVICES for differential pressure calculations, trap surveys, and quotations.